Harmonics on Board: Why Variable Speed Drives Distort a Ship's Power and How to Control It
Monthly Read · No. 1310 min readby Suji Kumar C
Thrusters, cargo pumps, ballast pumps, fans and electric propulsion increasingly run through variable speed drives (VFDs). They save fuel and give precise control. But a drive does not draw a smooth sine-wave current from the switchboard — it draws current in pulses. On a ship, where every load shares the same few generators, those pulses distort the voltage that every other consumer on board receives.
What Harmonics Are
A perfect AC supply is a single sine wave at 50 or 60 Hz. Non-linear loads — anything with a rectifier at its input, such as VFDs, battery chargers, UPS units and LED drivers — draw current in short peaks. Mathematically, that distorted current is the sum of the fundamental frequency plus components at whole multiples of it: the 5th, 7th, 11th, 13th harmonics and beyond. A standard 6-pulse drive mainly produces the 5th and 7th.
These harmonic currents flow back through cables and generators. Because generators have relatively high internal impedance compared with a land grid, the harmonic currents create harmonic voltage drops, and the voltage waveform at the main switchboard becomes distorted. The usual measure is Total Harmonic Distortion (THD): the size of all harmonic components relative to the fundamental, expressed as a percentage.
Source
Rectifier front ends in VFDs, chargers, UPS systems and electronic loads draw non-sinusoidal current.
Path
Harmonic currents flow through cables, transformers and generator windings, creating voltage distortion at the busbar.
Victims
Every other consumer on the same busbar receives the distorted voltage — motors, electronics, instruments and protection relays.
Why Ships Are More Sensitive Than Shore
On land, a factory's drives share a grid backed by huge generation capacity, so the same harmonic current produces very little voltage distortion. A ship is a weak island grid. With only two or three generators online at sea — and fewer in port — the same drive load can push distortion several times higher. The problem is worst at light generator loading with heavy drive loading, such as a dynamic-positioning vessel holding station on thrusters with a single generator running.
Overheating
Harmonic currents add losses in generators, transformers and motors, raising winding temperatures and shortening insulation life.
Electronic Malfunction
Distorted voltage upsets equipment that relies on a clean waveform — some power supplies, instruments and zero-crossing timing circuits.
Nuisance Trips & Resonance
Harmonics can make protection relays and breakers misoperate, and can excite resonance with capacitors in filters or lighting circuits.
Navigation & Comms Interference
High-frequency noise from drives can couple into sensitive bridge and communication equipment if cabling and earthing are poor.
What the Class Rules Require
Classification societies limit voltage distortion on the main switchboard. IACS Unified Requirement E24, Harmonic distortion for ship electrical distribution system including harmonic filters, sets a general limit of 8% THD for the distribution system. A higher limit can be accepted only where all installed equipment is designed for it and the relaxation is documented in a harmonic distortion calculation report kept on board. Some class rules and notations apply stricter limits for particular vessel types or systems.
E24 also deals with a quieter risk: harmonic filters that fail. Where filters are fitted on the main busbars, the ship must be able to monitor distortion continuously and alert the crew if it exceeds the limit; distortion must be measured and recorded under seagoing conditions and after changes to the electrical system; and the system integrator must show, by calculation, what happens to distortion if a filter fails, and give the owner guidance on safe operating modes.
Mitigation Options
There is no single best solution — the right choice depends on drive power, how many drives run at once, available space and the generator configuration. The options below run roughly from simplest to most capable.
| Method | How It Works | Where It Fits |
|---|---|---|
| Line reactors / DC chokes | Smooth the drive's input current, reducing harmonic peaks | Low-cost first step on smaller drives |
| 12- / 18- / 24-pulse drives | Phase-shifting transformers cancel the main low-order harmonics | Large propulsion and thruster drives |
| Passive filters | Tuned LC circuits absorb specific harmonics | Fixed, predictable loads; must be checked for resonance and failure |
| Active harmonic filters | Power electronics inject opposite currents to cancel measured harmonics | Mixed or changing loads, retrofits with limited space |
| Active front end (AFE) drives | A controlled transistor rectifier draws near-sinusoidal current | New builds and drive replacements where low distortion is designed in |
Measuring & Living With It
Harmonics are invisible on an ordinary voltmeter. They are measured with a power quality analyser that captures the waveform and calculates individual harmonic levels and THD, typically up to the 40th or 50th harmonic. The meaningful measurement is taken under the worst realistic condition — heavy drive load on the fewest generators — not on a quiet day alongside the berth.
Design Stage
Run a harmonic study using the actual drive data and generator impedances for every operating mode, including one-generator operation and filter failure.
Sea Trials
Measure THD at the main switchboard under representative load and keep the results as the ship's baseline.
In Service
Re-measure after any drive, filter or generator change. A creeping THD figure is often the first sign of a deteriorating filter.
- Harmonics
- Power Quality
- VFD
- IACS UR E24
- Marine Electrical
- THD